Floor area and insulation level to the heating load in kW and BTU per hour, and the heat pump size in tons your home needs.
A 150 square metre home with average insulation needs a heating load of about 11.25 kW, which is about 38,385 BTU per hour and about 3.2 tons. The next standard size up is a 42,000 BTU per hour unit, or 3.5 tons. A heat pump is sized from the heat the house loses on the coldest day, not from the floor area alone: the same 150 square metres needs only about 7.5 kW with good insulation and about 15 kW with poor insulation. Enter your own floor area and insulation level in the calculator above.
What size heat pump do I need?
Start with the heating load, which is the floor area times the heat loss per square metre for your insulation level. The table below uses average insulation at 75 W per square metre. The recommended size is the next standard size up, because a heat pump that is too small cannot hold the temperature on the coldest nights.
| Floor area | Heating load | Load in BTU/h | Load in tons | Recommended size |
|---|---|---|---|---|
| 100 m² | 7.5 kW | 25,590 | 2.1 | 30,000 BTU/h (2.5 ton) |
| 150 m² | 11.25 kW | 38,385 | 3.2 | 42,000 BTU/h (3.5 ton) |
| 200 m² | 15 kW | 51,180 | 4.3 | 60,000 BTU/h (5.0 ton) |
Check the table against the calculator: a 100 square metre home at average insulation needs about 7.5 kW, about 25,590 BTU per hour and about 2.1 tons, so a 30,000 BTU per hour unit. A 200 square metre home needs about 15 kW, about 51,180 BTU per hour and about 4.3 tons, so a 60,000 BTU per hour unit. One ton of heat pump capacity is 12,000 BTU per hour, and standard residential sizes run from 18,000 to 60,000 BTU per hour.
How insulation changes the size
Insulation moves the answer more than floor area does. The table below holds the floor area at 150 square metres and changes only the insulation level, using the same bands as our boiler size calculator: good at 50 W per square metre, average at 75 W and poor at 100 W.
| Insulation (150 m² home) | Heating load | Load in BTU/h | Load in tons | Recommended size |
|---|---|---|---|---|
| Good, 50 W/m² | 7.5 kW | 25,590 | 2.1 | 30,000 BTU/h (2.5 ton) |
| Average, 75 W/m² | 11.25 kW | 38,385 | 3.2 | 42,000 BTU/h (3.5 ton) |
| Poor, 100 W/m² | 15 kW | 51,180 | 4.3 | 60,000 BTU/h (5.0 ton) |
The same house needs twice the heat pump with poor insulation as it does with good insulation. That is why loft and cavity wall insulation often costs less than the larger heat pump it avoids. A newer, tighter house needs roughly a third less than the table shows, and an older, leaky one roughly half as much again.
What about cooling?
A heat pump has two jobs, and they pull the size in different directions. In summer it is an air conditioner and should be sized to the cooling load. In winter its heating output falls as the outdoor temperature drops, just when the house needs the most heat. Where winters are mild, cooling decides the size. Where they are cold, heating does, and the question becomes how much backup heat covers the coldest hours.
The cooling guide in the calculator uses about 600 square feet per ton, the rule Trane gives for existing homes. A 150 square metre home is about 1,615 square feet, so the cooling guide is about 3.0 tons. A 2,000 square foot home needs about 2.4 tons of cooling on the usual 850 square feet per ton basis, and a 2,000 square foot two-storey home in a mixed climate like Virginia loses about 28,500 BTU per hour on the coldest night, which is a 2.5-ton heat pump on the heating side.
Why a heat pump loses capacity in cold weather
Rated capacity is measured at 47 degrees Fahrenheit outdoors. Cold weather takes a large share of it: a standard heat pump keeps about 60% of its rated capacity at 17 degrees Fahrenheit and about 40% at 5 degrees Fahrenheit. A cold-climate heat pump keeps more, and in cold climates you should choose one with a COP of at least 3.5 at 5 degrees Fahrenheit. Check the capacity at your design temperature, not just the headline tonnage, and check the balance point, which is the outdoor temperature where the heat pump output equals the house heat loss. Below it, backup heat covers the rest.
When to get a Manual J calculation
This calculator gives a sizing estimate from floor area, climate and insulation, which is the right level for comparing sizes and budgets. A full ACCA Manual J calculation from a licensed HVAC engineer is the code-compliant route for an exact size, and it is worth getting for a multi-zone home, a home with high heat loss, or a home where the heating and cooling loads point to different sizes. The engineer measures each room, the windows, the air leakage and the local design temperature, and sizes the system room by room.
For the running cost once you know the size, see our heat pump cost calculator. For the gas alternative, see our furnace size calculator and our boiler size calculator.
Frequently asked questions
What size heat pump do I need for a 2,000 sq ft house?
About 13.9 kW, or about 47,548 BTU per hour, which is about 4.0 tons at average insulation, so a 48,000 BTU per hour (4 ton) unit. With good insulation the same house needs about 9.3 kW, about 31,700 BTU per hour and a 36,000 BTU unit, and with poor insulation about 18.6 kW, about 63,400 BTU per hour, which is above a single 60,000 BTU unit.
How many tons of heat pump per square foot?
For cooling, about 1 ton per 600 square feet in an existing home, and about 1 ton per 850 square feet on the usual design basis. For heating, the load depends on climate and insulation: 20 to 30 BTU per square foot in a mild climate, 30 to 45 in a moderate climate, and 40 to 60 or more in a cold climate. Use the heating load, not a single square-foot rule, to pick the size.
Is a bigger heat pump better?
No. A heat pump that is too large short-cycles, switching on and off in short bursts, which wears the compressor, leaves humidity high in summer and costs more to buy. A heat pump that is too small cannot hold the temperature on the coldest nights and leans on expensive backup heat. The right size is the smallest standard size that meets the design heating load.
What is a cold-climate heat pump?
A heat pump built to keep most of its capacity in cold weather, with a COP of at least 3.5 at 5 degrees Fahrenheit. A standard heat pump keeps about 60% of its rated capacity at 17 degrees Fahrenheit and about 40% at 5 degrees, so in a cold climate a standard model needs a larger size or more backup heat than a cold-climate model.
Sources
The standard residential sizes of 18,000 to 60,000 BTU per hour, the mild climate band of 20 to 30 BTU per square foot, the moderate band of 30 to 45 and the cold band of 40 to 60 or more, and the cold-climate COP of at least 3.5 at 5 degrees Fahrenheit follow a 2026 heat pump sizing calculator. The Carrier rule of 20 to 30 BTU per square foot, the Trane rule of about 600 square feet per ton for existing homes and up to 1,000 square feet per ton for new construction, and the degree-day method for sizing from fuel bills follow a heat pump size calculator updated in November 2026. The 2,000 square foot home needing about 29,600 BTU per hour in a cold climate and about 35,400 in a very cold climate, and the note that a newer, tighter house needs roughly a third less and an older, leaky one roughly half as much again, follow a 2026 heat pump sizing guide. The 2,000 square foot Virginia home losing about 28,500 BTU per hour and needing about 2.4 tons of cooling, the cooling basis of 850 square feet per ton, and the standard heat pump keeping about 60% of capacity at 17 degrees Fahrenheit and about 40% at 5 degrees follow a heat pump size calculator updated in November 2026.
Changelog
- 22 November 2026: calculator published.
Cite this page
APA: Wolveyes. (2026, November 22). Heat Pump Size Calculator. Wolveyes. https://wolveyes.pk/calculators/heat-pump-size-calculator/
MLA: “Heat Pump Size Calculator.” Wolveyes, 22 Nov. 2026, https://wolveyes.pk/calculators/heat-pump-size-calculator/
<iframe src="https://wolveyes.pk/calculators/heat-pump-size-calculator/" width="100%" height="600" style="border:1px solid #E5E0D5;border-radius:8px;" title="Heat Pump Size Calculator by Wolveyes"></iframe>
<p><a href="https://wolveyes.pk/calculators/heat-pump-size-calculator/">Heat Pump Size Calculator by Wolveyes</a></p>